One, characteristic and Application
The induced fan is a part of the airless induced jet ventilation system. It is composed of an air supply fan and an exhaust fan. The principle of the system is designed by a system designed, more than a number of guidance fan nozzle directed high speed air flow, the induction of outdoor air or treated air, under the condition of no wind pipe to the required area, to achieve the best indoor air flow organization, in order to achieve efficient and economical ventilation and ventilation effect. When using no pipe jet to induce ventilation system, the cost of designing, manufacturing and installing the wind pipe and other supporting works can be saved. This part is much more expensive than the induced fan unit used, and the ventilation duct of the ventilation fan and exhaust fan is much smaller than that of the pipe. The wind turbines with high wind volume and lower wind pressure can be used to reduce the required power and greatly reduce operation costs and investment costs. When the exhaust fan stops running, the induced fan can still work and play the role of partial ventilation and ventilation.
The fan is built with high efficiency centrifugal fan, low noise, small size, light weight, convenient hoisting (vertical and horizontal installation) and simple maintenance. It is widely used in underground parking lots, gymnasium, workshop, warehouse, supermarket, supermarket, entertainment and other large area ventilation.
The YDF- type I inducer fan is generally used in the induction ventilation system without wind pipes. There are two types of horizontal and horizontal and horizontal dual use structures. The motor uses a single phase motor for the fan.
YDF- II type induction fan is cabinet structure, horizontal installation and belt drive. The three phase induction motor is usually combined with a spiral air duct and a radially curved nozzle to form an inductive ventilation system with an air duct.
The air quality sensor can be set up in the induced space to detect the concentration of carbon monoxide and control the opening and stopping of the induction fan automatically by the controller to realize automatic control.
Two, the inductive ventilation system has advantages over the traditional duct ventilation system.
1. System planning and design is simple, design change flexibility is big, modification is easy, layout is flexible, the direction of injection can be adjusted at any time and anywhere.
2, easy installation, simple construction, can be installed in targeted locations, eliminate dead ends.
3, maintenance is simple and convenient, single machine maintenance, does not affect the operation of the entire system;
4, high air quality, induction system uses the entire space air circulation completely, without leaving dead ends, improving the air quality;
5. The fan is made of high quality cold rolled plate (super hard aluminum alloy frame), with plastic sprayed surface, beautiful appearance and good coordination with space decoration.
6, the motor adopts a special motor for maintenance free fan, and has built-in high efficiency centrifugal fan. The noise is low, and the impeller is calibrated by high-precision dynamic balance, and the vibration is small.
Three, performance parameters and shape size table

YDF系列性能参数表

型号
No

风量
(m3/h)

出口风速
(m/s)

功率
(w)

射程
(m)

重量
(Kg)

噪声
dB(A)

喷口直径
(mm)

YDF-I-6L

650-850

11-15

100

10

20

50

Φ80*3

YDF-I-6W

120

10

20

50

Φ80*3

YDF-I-12

1150-1350

14-24

180

15

35

58

Φ80*3

YDF-Z-2.2

1380

11-16

180

20

45

55

Φ175*1

YDF-II-2.25

2300

风压1300Pa

2200

/

130

80

Φ35*32

YDF-II-2.5

3600

风压1736Pa

3000

/

150

84

Φ35*36

YDF-II-2.8

6000

风压1760Pa

4000

/

180

87

Φ35*60


Four. Shape size and installation of nozzle
(1) schematic diagram of YDF- I -6L vertical induced draft fan (universal spherical nozzle)
The horizontal induction fan of the spherical nozzle is composed of a centrifugal fan, an anechoic box and three universal spherical nozzles. The angle of rotation is <60 degrees, and the nozzle is 80 * 3. Main features: the nozzle position increases 8, can adjust the nozzle position arbitrarily, adapt to the different design and the actual needs of the field, the unit does not change, the fan efficiency is improved.

Related Information
Home | About Us | Porducts | Technology | Contact us
Add:No.9,deYuRoad,ChengnanPark,Jingjiang,Jiangsu,ChinaTel:0523-84814391 Fax:0523-82859386
苏ICP备18037890号
在线客服
热球式风速传感器| 预埋槽| X射线应力分析仪| 泡沫棒| 日本CHINO千野IR| Datacolor800| NIPPONGEAR日本齿轮| 贴标机厂家| 高温高精度进料泵| LED光电试验箱| Bofa滤芯过滤器| 液氨泵| 药物凝点仪| PDS863液位变送器| 碎石冲击试验机| 四柱简易升降停车位| 波纹管柔韧性检测仪| 电磁阀就地控制箱| 青岛丹佳净化设备| 切削液废水处理设备| 陶瓷柱塞移液泵| 竖卷吊具| 火锅底料搅拌炒锅(全自动电磁行星炒锅)百科| 串联谐振耐压成套装置| 英飞凌igbt模块| 中央实验台厂家| Burkert宝德PH计| 无水隔膜真空泵| 氙灯老化试验箱| 氧化钙粉| 淄博碧泉水处理设备| 高性能空心阴极灯| 电加热元件| 成都生活污水处理设备| vaisala维萨拉备件| 实验室磷酸根| 日本AND水份仪维修| 信号灯报警灯扬声器| 超声波测厚仪厂家| 茶毛虫| 国产酶标仪|